Earth grounding is vital to protect our life and electrical facilities. It helps eliminate losses due to faulty installation and
reduces damage from lightning strikes and induced voltages. It covers and improves the performance of our electrical
equipment and home appliances. Over time, ground systems can degrade or become ineffective. Corrosion and weather
influences exert mechanical strain on ground rods and cause metallic corrosion. Catastrophic events like lightning strikes
or large fault currents can cause instant degradation to our systems. The risks from ground system deterioration may lead
to severe electrical shock, equipment damage, disruption in the performance of sensitive equipment and heat build-up on
issues.
Keeping an adequate low resistance ground connection is essential to the protection and performance of our electrical
system. To practise earth resistance testing should be regularly on installation and preventive service. In addition, soil
resistivity tests can be used in prospecting, locating, and designing new grounding electrodes and systems. It can help
make healthy environmental conditions and create different ground system needs.
BST's new ER-80 series 4-terminal ground testing instrument includes two models with automatic and manual operation
testing flexibility. Both models (ER-80A and ER-80M) employ measuring functions for ART (Attached Rod Technique)
testing capabilities. The basic kit includes the test leads, connectors/adapters, and a rugged carry case – everything you
need to start testing in one package.
The ER-80M can measure resistance from 0.030 Ω to 200 kΩ in 5 manual ranges; it is also capable of soil resistivity
testing (ρ). The ER-80M is powered by eight 1.5V R14SG Type C batteries, which are widely available. The tester is rated
IP54 for outdoor use with a safety design to CAT III 300 V.
• IP54 for outdoor environments
Features:
- Earth resistance measurement of 6 ranges: 0.030 Ω ~ 200 kΩ
- Ground rod technique (2, 3, 4 points) to automatically
calculate earth resistance
- Precision four-wire measurement of earth resistance or soil
resistivity
- Standard three-wire measurement of earth resistance
- Simple two-wire measurement of earth resistance
Ultra-wide viewing angle large screen FSTN LCD to display
multiple measurement results
- LED Backlight for easy readout in dim-lit environments
- A wide range of test frequencies can be selected automatically
or manually (94 Hz / 105 Hz / 111 Hz / 128 Hz)
- Compensate test cable resistance Rk function
- Can store 999 groups of data to check in real-time on display
or computer download via USB for further analysis
- Automatic shutdown (No operation for 10 minutes)
- Powered by 1.5V R14SG Type C x 8 Pcs.
- IP54 for outdoor environments
- EN-61010-1 CAT III 300V safety
TECHNICAL SPECIFICATIONS
EARTHING RESISTANCE
Range
Measuring Range
Resolution
Accuracy
2 Ω
0.030 ~ 2.099 Ω
0.001 Ω
±(3 % + 5dgt)
20 Ω
0.03 ~ 20.99 Ω
0.01 Ω
±(2 % + 5dgt)
200 Ω
0.1 ~ 209.9 Ω
0.1 Ω
±(2 % + 5dgt)
2000 Ω
1 ~ 2099 Ω
1 Ω
±(2 % + 5dgt)
20 kΩ
0.01 ~ 20.99 kΩ
0.01 kΩ
±(2 % + 5dgt)
200 kΩ
0.01 ~ 200.9 kΩ
0.1 kΩ
±(5 % + 5dgt)
SOIL RESISTIVITY MEASUREMENT "ρ"
Range
Measuring Range
Resolution
Accuracy
2 Ω
0.18 Ωm ~ 1.318 kΩ.m
0.001 Ω
ρ = 2 x Π x a x Rg
20 Ω
0.18 Ωm ~ 13.18 kΩ.m
0.01 Ω.m
ρ = 2 x Π x a x Rg
200 Ω
0.62 Ωm ~ 131.8 kΩ.m
0.1 Ω.m
ρ = 2 x Π x a x Rg
2000 Ω
6.28 Ωm ~ 1318 kΩ.m
1 Ω.m
ρ = 2 x Π x a x Rg
20 kΩ
62.80 Ωm ~ 1999 kΩ.m
0.01 kΩ.m
ρ = 2 x Π x a x Rg
200 kΩ
628.8 Ωm ~ 1999 kΩ.m
0.1 kΩ.m
ρ = 2 x Π x a x Rg
INTERFERENCE VOLTAGE MEASUREMENT "V"
Item
Range
Resolution
Accuracy
Interference Voltage (Ust)
50.0 V
0.1 V
±(2% + 2dgt)
Interference Voltage Frequency (Fst)
16 Hz ~ 500 Hz
0.1 Hz
±(1 % + 0.5 Hz)
GENERAL PARAMETERS
2/3/4 Wire Test
Available
Test Frequency
94 Hz / 105 Hz / 111 Hz / 128 Hz of AFC
Measuring Current
≤20 mA
Open Terminal Measurement Voltage
≤48 Vrms
Lead Resistance Removal (Rk)
Available
Automatic Power Off
10 Minutes (No Operation)
Storage Capacity
999 Sets of Measurement Data
Communication Interface
USB (Opto-Isolated)
LCD Display
FSTN ( 102 mm x 86.6 mm )
LCD Backlight
LED Backlight
Safety Standard
EN 61010-1:2010 CAT III 300V, EN 61326-1:2013, EN 61326-2-2:2013
Dimensions (W x L x D)
270 mm x 190 mm x 80 mm
Weight
~1700 g (Including Battery)
Battery
8 x 1.5V R14SG Type C
Accessories
Banana Plug + Alligator Clip Measurement Cable x 4,
Ground Rod x 4, Carry Case with Shoulder Strap x 1 &
Instruction Manual
Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without notice.